Residential Inspection Report

5240 Prairie Grass Lane

Colorado Springs, Colorado 80922

Year Built : 2000 Sq.Footage : 3171 Occupied : Occupied Utilities : Water, Gas, Electric, On Weather : Clear
  • Summary

    434 Items Inspected

    DEFECT #0 OF 0

    Roof Coverings and Drainage

    Roof Drainage Systems

    DEFICIENCY 2.1
    Detached Downspout - Gutters

    Estimated Severity : Minor/Maintenance

    One or more downspouts around the property were detached at the time of the inspection. Recommend repair ...

    Exterior

    Walkways Patios Driveways

    DEFICIENCY 3.1
    Cracking/Settling - Minor - Walkways Patios Driveways

    Estimated Severity : Minor/Maintenance

    I observed some minor cracks in the cement. This is very typical due to soil movement. I would consider ...

    Exterior

    Vegetation Grading Drainage Retaining Walls

    DEFICIENCY 3.2
    Negative Grading - Landscaping

    Estimated Severity : ⚠️ Repair

    Grading is sloping toward the home in one or more areas. This could lead to water intrusion and foundatio...

    Exterior

    Siding Flashing Trim

    DEFICIENCY 3.3
    Water Intrusion and Dry Rot - Siding/Trim

    Estimated Severity : Minor/Maintenance

    Siding showed signs of water intrusion. This could lead to further siding deterioration. Recommend a qual...

    Exterior

    Siding Flashing Trim

    DEFICIENCY 3.4
    Seal Maintenance - Siding/Trim

    Estimated Severity : Minor/Maintenance

    Caulking is failing at seams where siding meets trim, transitions, or is penetrated. I recommend monitori...

    Exterior

    Siding Flashing Trim

    DEFICIENCY 3.5
    Typical Wear For The Age - Siding/Trim

    Estimated Severity : Minor/Maintenance

    The siding and trim had minor signs of wear, peeling paint and maintenance needed typical for the age of ...

    Exterior

    Siding Flashing Trim

    DEFICIENCY 3.6
    Damaged - Siding/Trim

    Estimated Severity : ⚠️ Repair

    There appears to be one or more areas of damaged siding. Recommend replacement or repair of siding.

    Exterior

    Windows

    DEFICIENCY 3.7
    Debris - Window Wells

    Estimated Severity : Minor/Maintenance

    Debris has accumulated in the window wells. I recommend removal before mold, flooding, deterioration or o...

    Exterior

    Windows

    DEFICIENCY 3.8
    Damaged/Failure - Window Well

    Estimated Severity : ⚠️ Repair

    Window wells show signs of failure. Recommend having evaluated by landscaper / gardener for repair or rep...

    Exterior

    Fence

    DEFICIENCY 3.9
    Typical Wear For The Age - Fence

    Estimated Severity : Minor/Maintenance

    The fence showed signs of typical wear, splitting, sagging and aging. I recommend repair as needed.

    Garage

    Garage Door

    DEFICIENCY 4.1
    Weatherstripping Damaged/missing - Garage Door

    Estimated Severity : ⚠️ Repair

    I recommend repair or replace.

    Garage

    Garage Door Opener & Safety

    DEFICIENCY 4.2
    Reduce Resistance Setting - Garage Door Opener

    Estimated Severity : ⚠️ Repair

    The garage door opener's safety settings was not functioning properly during the inspection. When the ope...

    Electrical

    Main Subpanels Service Grounding Main Overcurrent Device

    DEFICIENCY 5.1
    Improperly Wired Sub Panel

    Estimated Severity : Potential Safety Concern 📛

    The sub panel does not appear to be wired properly on the neutral buss bar recomend repair.

    Electrical

    Branch Wiring Circuits Breakers Fuses

    DEFICIENCY 5.2
    Loose and/or Exposed Wiring

    Estimated Severity : Potential Safety Concern 📛

    There is unsafe and exposed wiring visible and present during the home inspection. I recommend a licensed...

    Electrical

    GFCI AFCI

    DEFICIENCY 5.3
    GFCI Protection Not Installed

    Estimated Severity : ⚠️ Repair

    There are receptacles in the home that aren't protected by GFCI when they should be. Receptacles near wat...

    Electrical

    Lighting Fixtures Switches Receptacles

    DEFICIENCY 5.4
    Damaged - Cover Plates

    Estimated Severity : ⚠️ Repair

    I found one or more receptacles that had damaged cover plates. The cover plates are important to prevent ...

    Electrical

    Lighting Fixtures Switches Receptacles

    DEFICIENCY 5.5
    Inoperable - Light Fixture

    Estimated Severity : Minor/Maintenance

    Light was not operating during the inspection. It could be just a simple light bulb that is burnt out, bu...

    Electrical

    Lighting Fixtures Switches Receptacles

    DEFICIENCY 5.6
    Inoperable - Ceiling Fan

    Estimated Severity : ⚠️ Repair

    There is a ceiling fan that was inoperable at time of inspection recommend repair.

    Electrical

    Lighting Fixtures Switches Receptacles

    DEFICIENCY 5.7
    Improperly Wired 3 Way - Switch

    Estimated Severity : Potential Safety Concern 📛

    A 3 way switch is improperly wired. I recommend a licensed electrician repair or replace.

    Electrical

    Smoke Detectors

    DEFICIENCY 5.8
    Missing - Smoke Detectors

    Estimated Severity : Potential Safety Concern 📛

    Smoke detectors were missing at the time of inspection. I recommend installation.

    Electrical

    Smoke Detectors

    DEFICIENCY 5.9
    Expired - Smoke Detectors

    Estimated Severity : Potential Safety Concern 📛

    The smoke detectors appeared older as evidenced by the yellowing of the plastic and may be expired. I rec...

    Electrical

    Smoke Detectors

    DEFICIENCY 5.10
    Hanging - Smoke Detector

    Estimated Severity : ⚠️ Repair

    One or more smoke detectors were hanging from the power wires at the time of the inspection. Recommend en...

    Electrical

    Smoke Detectors

    DEFICIENCY 5.11
    Battery Missing - Smoke Detector

    Estimated Severity : Potential Safety Concern 📛

    One or more smoke detectors had the battery missing at the time of the inspection. Recommend replacement.

    Heating

    Equipment

    DEFICIENCY 7.1
    Clean/Service - Furnace

    Estimated Severity : ⚠️ Repair

    The furnace is dirty. I recommend servicing by a qualified HVAC technician.

    Heating

    Gas/LP Firelogs & Fireplaces

    DEFICIENCY 7.2
    Foggy glass - Fireplace

    Estimated Severity : Minor/Maintenance

    The glass on the gas fireplace was foggy at the time of the inspection. Recommend cleaning of glass.

    Cooling

    Cooling Equipment

    DEFICIENCY 8.3
    Damaged Fins - Major - Exterior Condenser

    Estimated Severity : ⚠️ Repair

    While inspecting the AC condenser, I found major damage to the fins. I suspect that the damage was done b...

    Cooling

    Cooling Equipment

    DEFICIENCY 8.5
    Missing/Damaged - Insulation for A/C

    Estimated Severity : Minor/Maintenance

    Missing or damaged insulation on refrigerant line can cause energy loss and condensation. I recommend hav...

    Plumbing

    Water Supply

    DEFICIENCY 9.2
    Corrosion - Supply Pipes

    Estimated Severity : Minor/Maintenance

    Pipe and/or fittings were observed to have corrosion. This can lead to a shortened lifespan. Recommend a ...

    Plumbing

    Water Heater

    DEFICIENCY 9.3
    Dated Water Heater

    Estimated Severity : Minor/Maintenance

    The expected lifespan of a water heater is 8 to 12 years. One or more of the water heaters in the home fe...

    Plumbing

    Fixtures

    DEFICIENCY 9.4
    Loose - Toilet

    Estimated Severity : ⚠️ Repair

    The toilet was loose at the base. This may be from a damaged flange or a failed wax seal. In any case, th...

    Plumbing

    Fixtures

    DEFICIENCY 9.5
    Maintain Caulking - Plumbing fixture

    Estimated Severity : Minor/Maintenance

    The caulking around the fixture was in need of repair and/or maintenance. Water intrusion can become a co...

    Plumbing

    Fixtures

    DEFICIENCY 9.6
    Not Functioning - Drain Assembly

    Estimated Severity : Minor/Maintenance

    The drain stopper at the fixture was missing or not functioning. Repair or replace.

    Plumbing

    Fixtures

    DEFICIENCY 9.7
    Grout Maintenance

    Estimated Severity : Minor/Maintenance

    Recommend re-grouting. 

    Doors Windows Interior

    General

    DEFICIENCY 10.1
    Damage drywall

    Estimated Severity : Minor/Maintenance

    minor drywall damage was present at time of inspection

    Doors Windows Interior

    Windows

    DEFICIENCY 10.2
    Failed Seal - Window

    Estimated Severity : ⚠️ Repair

    I observed condensation between the window panes, which indicates a failed seal. The windows have lost ef...

    Doors Windows Interior

    Windows

    DEFICIENCY 10.3
    Damaged Screen - Window

    Estimated Severity : Minor/Maintenance

    I recommend repair or replacement of the screen.

    Doors Windows Interior

    Windows

    DEFICIENCY 10.4
    Missing Screen - Window

    Estimated Severity : Minor/Maintenance

    When inspecting the windows, I did find that one or more of them did not have screens. I recommend replac...

    Doors Windows Interior

    Windows

    DEFICIENCY 10.5
    Caulk Maintenance - Window

    Estimated Severity : Minor/Maintenance

    I did find one or more windows in the home that need to be caulked on the interior side. Caulking on the ...

    Doors Windows Interior

    Walls

    DEFICIENCY 10.6
    Paint touch up

    Estimated Severity : Minor/Maintenance

    At the time of inspection there were one or more locations that were in need of paint touch up on the wal...

    Insulation Ventilation

    Crawlspace / Basement Wall Insulation

    DEFICIENCY 12.1
    Insulation missing or damaged - Basement

    Estimated Severity : Minor/Maintenance

    Insulation covering foundation walls was missing, damaged, or had fallen down in one or more places. Reco...

    Insulation Ventilation

    Attic Insulation

    DEFICIENCY 12.2
    Uneven Insulation - Attic

    Estimated Severity : Minor/Maintenance

    Recommend leveling insulation for even insulating properties throughout the attic space.

    Lateral Sewer Line

    Sewer Scope

    DEFICIENCY 13.1
    Blockage - Laterial Sewer Line

    Estimated Severity : Potential Safety Concern 📛

    The lateral sewer line had major debris or blockage at the time of inspection. This is restricting sewage...

Report Remarks

A home inspection is a non-invasive, visual examination of the accessible areas of the property, designed to identify areas of concern within specific systems or components defined by the signed agreements and Standards of Practice, that are both observed and deemed material by the inspector at the exact date and time of inspection. Any and all recommendations for repair, replacement, evaluation, and maintenance issues found, should be evaluated by the appropriate trades contractors within the client's inspection contingency window or prior to closing, which is contract applicable, in order to obtain proper dollar amount estimates on the cost of said repairs and also because these evaluations could uncover more potential issues than are able to be noted from a purely visual inspection of the property.

This inspection will not reveal every concern or issue that exists, but only those material defects that were observable on the day of the inspection. This inspection is intended to assist in evaluating the overall condition of the dwelling only. A Home Inspection is not a code inspection. We recommend that you check with your local building department for any closed, voided, failed or unpermitted work prior to closing on the home. This inspection does not predict future conditions and conditions with the property are subject to change the moment we leave the premises.

A home inspection is designed to reflect, as accurately as possible, the visible condition of the home at the time of the inspection. Conditions of a home for sale can change radically in only a day or two, so a home inspection is not meant to guarantee the condition of the home on the date of the sale, for example. It’s not uncommon for conditions to change between the time of the inspection and the closing date.

This chart details the predicted life expectancy of household materials, systems, and components. Life expectancy varies with usage, weather, installation, maintenance, and quality of materials. This chart provides a general guideline from the world's largest inspection association https://www.nachi.org/life-expectancy.htm

To review our Standards of Practice, view... https://www.nachi.org/sop.htm

Inspection Details Info

  • General : In AttendanceBuyer Agent
  • General : OccupancyOccupied
  • General : Style of Home2 story, With Basement
  • General : UtilitiesWater, Gas, Electric, On
  • General : WeatherClear
  • General : Temperature51

Roof Coverings and Drainage

Roof Drainage Systems

DEFICIENCY 2.1
Detached Downspout - Gutters

Estimated Severity : Minor/Maintenance

One or more downspouts around the property were detached at the time of the inspection. Recommend repair or replacement.

Roof Coverings and Drainage Info

  • General : Inspection MethodGround, Ladder, At Gutters
  • General : Roof Type / StyleGable
  • Coverings : MaterialAsphalt, Architectural
  • Roof Drainage Systems : Gutter MaterialAluminum
  • Flashings : MaterialSteel
  • Skylights, Chimneys & Other Roof Penetrations : Plumbing VentsYes, Satisfactory
  • Skylights, Chimneys & Other Roof Penetrations : Roof VentsYes, Satisfactory
  • Skylights, Chimneys & Other Roof Penetrations : Vents (Bathroom, Laundry)Yes, Satisfactory
  • Skylights, Chimneys & Other Roof Penetrations : SkylightNo
  • Skylights, Chimneys & Other Roof Penetrations : ChimneyNo
  • Skylights, Chimneys & Other Roof Penetrations : FlueYes, Satisfactory
  • Skylights, Chimneys & Other Roof Penetrations : Roof Safety AnchorsNo
  • Skylights, Chimneys & Other Roof Penetrations : Swamp CoolerNo
  • Skylights, Chimneys & Other Roof Penetrations : SolarNo
To view additional Roof Coverings and Drainage Photos, Click Here.
Cracking/Settling - Minor - Walkways Patios  Driveways
Cracking/Settling - Minor - Walkways Patios  Driveways

Exterior

Walkways Patios Driveways

DEFICIENCY 3.1
Cracking/Settling - Minor - Walkways Patios Driveways

Estimated Severity : Minor/Maintenance

I observed some minor cracks in the cement. This is very typical due to soil movement. I would consider these cracks cosmetic, but I do recommend using a sealant to prevent water intrusion. Monitor and maintain as necessary.

Negative Grading - Landscaping
Negative Grading - Landscaping
diagrams

Exterior

Vegetation Grading Drainage Retaining Walls

DEFICIENCY 3.2
Negative Grading - Landscaping

Estimated Severity : ⚠️ Repair

Grading is sloping toward the home in one or more areas. This could lead to water intrusion and foundation issues. I recommend qualified landscaper or foundation contractor re-grade so water flows away from home.

Exterior

Siding Flashing Trim

DEFICIENCY 3.3
Water Intrusion and Dry Rot - Siding/Trim

Estimated Severity : Minor/Maintenance

Siding showed signs of water intrusion. This could lead to further siding deterioration. Recommend a qualified siding contractor evaluate and repair. 

Exterior

Siding Flashing Trim

DEFICIENCY 3.4
Seal Maintenance - Siding/Trim

Estimated Severity : Minor/Maintenance

Caulking is failing at seams where siding meets trim, transitions, or is penetrated. I recommend monitoring and replacing caulk when needed.

Exterior

Siding Flashing Trim

DEFICIENCY 3.5
Typical Wear For The Age - Siding/Trim

Estimated Severity : Minor/Maintenance

The siding and trim had minor signs of wear, peeling paint and maintenance needed typical for the age of the home. Recommend monitoring and performing all maintenance as needed.

Damaged  - Siding/Trim
Damaged  - Siding/Trim

Exterior

Siding Flashing Trim

DEFICIENCY 3.6
Damaged - Siding/Trim

Estimated Severity : ⚠️ Repair

There appears to be one or more areas of damaged siding. Recommend replacement or repair of siding.

Exterior

Windows

DEFICIENCY 3.7
Debris - Window Wells

Estimated Severity : Minor/Maintenance

Debris has accumulated in the window wells. I recommend removal before mold, flooding, deterioration or other issues occur.

Exterior

Windows

DEFICIENCY 3.8
Damaged/Failure - Window Well

Estimated Severity : ⚠️ Repair

Window wells show signs of failure. Recommend having evaluated by landscaper / gardener for repair or replacement.

Exterior

Fence

DEFICIENCY 3.9
Typical Wear For The Age - Fence

Estimated Severity : Minor/Maintenance

The fence showed signs of typical wear, splitting, sagging and aging. I recommend repair as needed.

Exterior Info

  • General : Inspection MethodVisual
  • Walkways Patios Driveways : Driveway MaterialConcrete
  • Walkways Patios Driveways : Walkwaysconcrete
  • Siding Flashing Trim : Siding MaterialBrick, Composite hardboard
  • Siding Flashing Trim : Siding StylePanels, Brick
  • Eaves Soffits Fascia : MaterialFiber Cement
  • Exterior Doors : Exterior Entry Door TypesStorm Door, Metal
  • Windows : WindowsVinyl
  • Decks Balconies Porches Steps : StructureFront Porch, Back Patio
  • Decks Balconies Porches Steps : MaterialConcrete
  • Fence : FenceYes
To view additional Exterior Photos, Click Here.

Garage

Garage Door

DEFICIENCY 4.1
Weatherstripping Damaged/missing - Garage Door

Estimated Severity : ⚠️ Repair

I recommend repair or replace.

Garage

Garage Door Opener & Safety

DEFICIENCY 4.2
Reduce Resistance Setting - Garage Door Opener

Estimated Severity : ⚠️ Repair

The garage door opener's safety settings was not functioning properly during the inspection. When the opener is bringing the door down and upward pressure is applied, the door should go back up. I recommend having the resistance settings adjusted to ensure proper safety. This can usually be accomplished by consulting the user manual for the opener equipment. It is usually a very simple adjustment.

Garage Info

  • General : AttachedYes
  • General : DetachedNo
  • General : CarportNo
  • Floor : MaterialConcrete
  • Non-Fire Rated Walls & Ceilings : Type of wallExposed wall
  • Fire Rated Walls & Ceilings : Fire wall conditionSatisfactory
  • Garage Door : MaterialWood, Wood Composite
  • Garage Door : TypeSectional
  • Garage Door Opener & Safety : Resistance SettingsNeeds Adjustment
  • Garage Door Opener & Safety : Sensor Height - Garage Door OpenerGood
  • Garage Door Opener & Safety : SensorsFunctioning
  • Occupant Door (From garage to inside of home) : Fire DoorYes
To view additional Garage Photos, Click Here.

Electrical

Main Subpanels Service Grounding Main Overcurrent Device

DEFICIENCY 5.1
Improperly Wired Sub Panel

Estimated Severity : Potential Safety Concern 📛

The sub panel does not appear to be wired properly on the neutral buss bar recomend repair.

Electrical

Branch Wiring Circuits Breakers Fuses

DEFICIENCY 5.2
Loose and/or Exposed Wiring

Estimated Severity : Potential Safety Concern 📛

There is unsafe and exposed wiring visible and present during the home inspection. I recommend a licensed electrician repair and secure properly. 

Electrical

GFCI AFCI

DEFICIENCY 5.3
GFCI Protection Not Installed

Estimated Severity : ⚠️ Repair

There are receptacles in the home that aren't protected by GFCI when they should be. Receptacles near water sources, in garages, and outside need to be GFCI in order to prevent accidental shocks. I recommend having an electrician evaluate the home's receptacles in order to ensure safety.Here is a link to read about how GFCI receptacles keep you safe.

Electrical

Lighting Fixtures Switches Receptacles

DEFICIENCY 5.4
Damaged - Cover Plates

Estimated Severity : ⚠️ Repair

I found one or more receptacles that had damaged cover plates. The cover plates are important to prevent electrical shock and to protect the electrical connections, so I recommend replacing the plates.

Inoperable - Light Fixture
Inoperable - Light Fixture

Electrical

Lighting Fixtures Switches Receptacles

DEFICIENCY 5.5
Inoperable - Light Fixture

Estimated Severity : Minor/Maintenance

Light was not operating during the inspection. It could be just a simple light bulb that is burnt out, but I recommend communicating with the seller to determine if the light does actually function.

Inoperable - Ceiling Fan
Inoperable - Ceiling Fan

Electrical

Lighting Fixtures Switches Receptacles

DEFICIENCY 5.6
Inoperable - Ceiling Fan

Estimated Severity : ⚠️ Repair

There is a ceiling fan that was inoperable at time of inspection recommend repair.

Electrical

Lighting Fixtures Switches Receptacles

DEFICIENCY 5.7
Improperly Wired 3 Way - Switch

Estimated Severity : Potential Safety Concern 📛

A 3 way switch is improperly wired. I recommend a licensed electrician repair or replace.

Electrical

Smoke Detectors

DEFICIENCY 5.8
Missing - Smoke Detectors

Estimated Severity : Potential Safety Concern 📛

Smoke detectors were missing at the time of inspection. I recommend installation.

Electrical

Smoke Detectors

DEFICIENCY 5.9
Expired - Smoke Detectors

Estimated Severity : Potential Safety Concern 📛

The smoke detectors appeared older as evidenced by the yellowing of the plastic and may be expired. I recommend replacing every 10 years per manufacuters requirements.

Electrical

Smoke Detectors

DEFICIENCY 5.10
Hanging - Smoke Detector

Estimated Severity : ⚠️ Repair

One or more smoke detectors were hanging from the power wires at the time of the inspection. Recommend ensuring they work and properly installing them.

Electrical

Smoke Detectors

DEFICIENCY 5.11
Battery Missing - Smoke Detector

Estimated Severity : Potential Safety Concern 📛

One or more smoke detectors had the battery missing at the time of the inspection. Recommend replacement.

Electrical Info

  • Service Entrance Conductors : Electrical Service ConductorsBelow Ground, 240V
  • Main Subpanels Service Grounding Main Overcurrent Device : Main Panel LocationGarage
  • Main Subpanels Service Grounding Main Overcurrent Device : Panel Capacity200 AMP
  • Main Subpanels Service Grounding Main Overcurrent Device : Panel ManufacturerGeneral Electric
  • Main Subpanels Service Grounding Main Overcurrent Device : Panel TypeCircuit Breaker
  • Main Subpanels Service Grounding Main Overcurrent Device : Sub Panel LocationBasement
  • Branch Wiring Circuits Breakers Fuses : Branch WiringCopper, Aluminum Strand
  • Branch Wiring Circuits Breakers Fuses : Wiring MethodConduit, Romex
  • GFCI AFCI : Location testedOn outlets
  • Lighting Fixtures Switches Receptacles : Represenative Number TestedYes, Satisfactory
  • Lighting Fixtures Switches Receptacles : Ceiling fansYes, Satisfactory
  • Smoke Detectors : Type of smoke detectorsHardwired
  • Carbon Monoxide Detectors : Type of COoutlet
To view additional Electrical Photos, Click Here.

Foundation and Structure

General

LIMITATION 6.1
Insulated / Finished Walls Disclaimer

Foundation basement or crawlspace walls were finished and/or insulated at the time of inspection. Only walls which were fully exposed could be thoroughly inspected for structural deficiencies.

Foundation and Structure Info

  • General : Inspection MethodVisual
  • Foundation : MaterialConcrete
  • Foundation : StyleSlab on Grade
  • Floor / Ceiling Structure : MaterialTJIs
  • Floor / Ceiling Structure : Sub-floorOSB
  • Floor / Ceiling Structure : Basement/Crawlspace FloorUnobservable
  • Wall Structure : wall construction typeNon Floating Walls, Floating Walls
  • Wall Structure : Material2 x 4 Wood Studs
  • Roof Structure : Decking MaterialOSB
  • Roof Structure : Truss TypeManufactured Truss
To view additional Foundation and Structure Photos, Click Here.

Heating

Equipment

DEFICIENCY 7.1
Clean/Service - Furnace

Estimated Severity : ⚠️ Repair

The furnace is dirty. I recommend servicing by a qualified HVAC technician.

Foggy glass - Fireplace
Foggy glass - Fireplace

Heating

Gas/LP Firelogs & Fireplaces

DEFICIENCY 7.2
Foggy glass - Fireplace

Estimated Severity : Minor/Maintenance

The glass on the gas fireplace was foggy at the time of the inspection. Recommend cleaning of glass.

Heating Info

  • General : AFUE RatingAFUE (Annual fuel utilization efficiency) is a metric used to measure furnace efficiency in converting fuel to energy. A higher AFUE rating means greater energy efficiency. 90% or higher meets the Department of Energy's Energy Star program standard.
  • Equipment : BrandCarrier
  • Equipment : Energy SourceGas
  • Equipment : Heat TypeForced Air
  • Normal Operating Controls : ThermostatYes
  • Distribution Systems : DuctworkNon-insulated, Non-observable
  • Presence of Installed Heat Source in Each Room : LocationCeiling, Floor Surface
  • Presence of Installed Heat Source in Each Room : TypeRegister
  • Gas/LP Firelogs & Fireplaces : Working conditionYes
To view additional Heating Photos, Click Here.

Cooling

General

LIMITATION 8.1
Unable to Test Functionality

Due to the temperature being below 65, or the condenser being covered, it could not be tested at the time of the inspection.

Cooling

Cooling Equipment

DEFICIENCY 8.2
Corrosion - Exterior Condenser

Estimated Severity : ⚠️ Repair

There are signs of exterior wear and rust on the unit recommend an evaluation and repair if needed.

Cooling

Cooling Equipment

DEFICIENCY 8.3
Damaged Fins - Major - Exterior Condenser

Estimated Severity : ⚠️ Repair

While inspecting the AC condenser, I found major damage to the fins. I suspect that the damage was done by hail and I recommend having the damage evaluated by an HVAC technician to determine whether repair or replacement is necessary.

Damaged fins- Minor - Exterior Condenser
Damaged fins- Minor - Exterior Condenser

Cooling

Cooling Equipment

DEFICIENCY 8.4
Damaged fins- Minor - Exterior Condenser

Estimated Severity : ⚠️ Repair

While inspecting the condenser, I found minor damage to the fins. This type of damage can typically be repaired by an HVAC technician by using a special comb to straighten the fins back out. I recommend having an HVAC do an evaluation and repair as necessary.

Cooling

Cooling Equipment

DEFICIENCY 8.5
Missing/Damaged - Insulation for A/C

Estimated Severity : Minor/Maintenance

Missing or damaged insulation on refrigerant line can cause energy loss and condensation. I recommend having condensate lines insulated to improve unit efficiency.

Cooling

Cooling Equipment

DEFICIENCY 8.6
Dirty Fins - Exterior Condenser

Estimated Severity : ⚠️ Repair

Recommend cleaning fins to ensure proper airflow.

Cooling Info

  • Cooling Equipment : BrandCarrier
  • Cooling Equipment : Energy Source/TypeElectric, Central Air Conditioner
  • Cooling Equipment : LocationLeft Side of Home
  • Cooling Equipment : SEER Ratingunknown
  • Normal Operating Controls : ThermostatYes
  • Distribution System : ConfigurationCentral
  • Presence of Installed Cooling Source in Each Room : LocationCeiling, Floor Surface
To view additional Cooling Photos, Click Here.

Plumbing

Sprinkler System

LIMITATION 9.1
Not tested - Sprinkler System

Irriagation system not tested

Plumbing

Water Supply

DEFICIENCY 9.2
Corrosion - Supply Pipes

Estimated Severity : Minor/Maintenance

Pipe and/or fittings were observed to have corrosion. This can lead to a shortened lifespan. Recommend a qualified plumber repair.

Plumbing

Water Heater

DEFICIENCY 9.3
Dated Water Heater

Estimated Severity : Minor/Maintenance

The expected lifespan of a water heater is 8 to 12 years. One or more of the water heaters in the home fell within that range or past.

Loose - Toilet
Loose - Toilet

Plumbing

Fixtures

DEFICIENCY 9.4
Loose - Toilet

Estimated Severity : ⚠️ Repair

The toilet was loose at the base. This may be from a damaged flange or a failed wax seal. In any case, this should be remedied before a leak occurs.

Maintain Caulking - Plumbing fixture
Maintain Caulking - Plumbing fixture

Plumbing

Fixtures

DEFICIENCY 9.5
Maintain Caulking - Plumbing fixture

Estimated Severity : Minor/Maintenance

The caulking around the fixture was in need of repair and/or maintenance. Water intrusion can become a costly repair. I recommend sealing with a flexible caulk or silicone and then annual maintenance.

Plumbing

Fixtures

DEFICIENCY 9.6
Not Functioning - Drain Assembly

Estimated Severity : Minor/Maintenance

The drain stopper at the fixture was missing or not functioning. Repair or replace.

Plumbing

Fixtures

DEFICIENCY 9.7
Grout Maintenance

Estimated Severity : Minor/Maintenance

Recommend re-grouting. 

Plumbing Info

  • General : FiltersNone
  • General : Water SourcePublic
  • Main Water Shut-off : LocationBasement
  • Drain, Waste, & Vent Systems : Drain Size1 1/2", 2", 3"
  • Drain, Waste, & Vent Systems : MaterialPVC
  • Water Supply : Distribution MaterialCopper, Pex
  • Water Supply : Water Supply MaterialCopper
  • Water Heater : ManufacturerGE
  • Water Heater : Power Source/TypeGas
  • Water Heater : Capacity50
  • Water Heater : LocationBasement
  • Water Heater : Hot Water Function at FixtureWorking
  • Gas Supply : Main Gas Shut-Off LocationGas Meter
  • Fixtures : funtioning at the time of the InspectionYes, Satisfactory
  • Sump Pump : LocationBasement
To view additional Plumbing Photos, Click Here.

Doors Windows Interior

General

DEFICIENCY 10.1
Damage drywall

Estimated Severity : Minor/Maintenance

minor drywall damage was present at time of inspection

Doors Windows Interior

Windows

DEFICIENCY 10.2
Failed Seal - Window

Estimated Severity : ⚠️ Repair

I observed condensation between the window panes, which indicates a failed seal. The windows have lost efficiency and have a cloudy look. I recommend having a qualified window contractor evaluate.

Doors Windows Interior

Windows

DEFICIENCY 10.3
Damaged Screen - Window

Estimated Severity : Minor/Maintenance

I recommend repair or replacement of the screen.

Doors Windows Interior

Windows

DEFICIENCY 10.4
Missing Screen - Window

Estimated Severity : Minor/Maintenance

When inspecting the windows, I did find that one or more of them did not have screens. I recommend replacing the missing screens.

Doors Windows Interior

Windows

DEFICIENCY 10.5
Caulk Maintenance - Window

Estimated Severity : Minor/Maintenance

I did find one or more windows in the home that need to be caulked on the interior side. Caulking on the interior side is not only for cosmetic reasons, but also to weatherize the window. I recommend using a flexible and paintable caulking, and maintain over the years. 

Doors Windows Interior

Walls

DEFICIENCY 10.6
Paint touch up

Estimated Severity : Minor/Maintenance

At the time of inspection there were one or more locations that were in need of paint touch up on the walls.

Doors Windows Interior Info

  • Doors : ConditionSatisfactory but may need future adjustment
  • Windows : Window TypeDouble-hung, Single-hung
  • Windows : Window ManufacturerChampion, Alenco
  • Floors : Floor CoveringsHardwood, Tile
  • Walls : Wall MaterialTextured
  • Ceilings : Ceiling MaterialTextured
  • Steps, Stairways & Railings : Location2nd floor, basement
  • Countertops & Cabinets : Countertop MaterialQuartz, Hard Surface
  • Countertops & Cabinets : CabinetryWood
To view additional Doors Windows Interior Photos, Click Here.

Appliances Info

  • Dishwasher : BrandMiele
  • Refrigerator : BrandSamsung
  • Refrigerator : Ice and Water DispenserYes
  • Refrigerator : Working at Time of InspectionYes
  • Range/Oven/Cooktop : Range/Oven Energy SourceElectric
  • Range/Oven/Cooktop : Range/Oven BrandFrigidaire
  • Range/Oven/Cooktop : Exhaust Hood TypeRe-circulate
  • Range/Oven/Cooktop : Working at Time of Inspection Range/Oven/CooktopYes
  • Range Hood : FunctioningYes
  • Built-in Microwave : BrandLG
  • Built-in Microwave : Working at time of inspection - Built-in MicrowaveYes
  • Garbage Disposal : Working conditionYes
  • Clothes Dryer : BrandLG
  • Clothes Dryer : Power Source220V Electric
  • Clothes Dryer : Vent MethodMetal - Flex
  • Clothes Dryer : Working condition at time of inspectionYes
  • Clothes Washer : BrandLG
  • Clothes Washer : Working condition at time of inspectionYes
To view additional Appliances Photos, Click Here.

Insulation Ventilation

Crawlspace / Basement Wall Insulation

DEFICIENCY 12.1
Insulation missing or damaged - Basement

Estimated Severity : Minor/Maintenance

Insulation covering foundation walls was missing, damaged, or had fallen down in one or more places. Recommend repair or replacement to fully insulate foundation walls.

Insulation Ventilation

Attic Insulation

DEFICIENCY 12.2
Uneven Insulation - Attic

Estimated Severity : Minor/Maintenance

Recommend leveling insulation for even insulating properties throughout the attic space.

Insulation Ventilation Info

  • Crawlspace / Basement Wall Insulation : R-Value11
  • Crawlspace / Basement Wall Insulation : Insulation TypeBatt
  • Flooring Insulation : Insulation TypeNone
  • Exterior / Interior Wall Insulation : R-Valuena
  • Exterior / Interior Wall Insulation : Insulation TypeUnobservable
  • Attic Insulation : Insulation TypeFiberglass
  • Attic Insulation : R-Valuena
  • Ventilation : Ventilation TypeGable Vents
  • Exhaust Systems : Exhaust FansFan Only
  • Radon Mitigation System : Conditionnone
To view additional Insulation Ventilation Photos, Click Here.

Lateral Sewer Line

Sewer Scope

DEFICIENCY 13.1
Blockage - Laterial Sewer Line

Estimated Severity : Potential Safety Concern 📛

The lateral sewer line had major debris or blockage at the time of inspection. This is restricting sewage flow and will lead to a backup. Recommend cleaning and re-inspection of the lateral line by a qualified professional.

Lateral Sewer Line Info

  • Sewer Scope : Distance Scoped38 meters
  • Sewer Scope : LocationsClean-out Basement
  • Sewer Scope : Pipe MaterialPVC
  • Sewer Scope : Overall ConditionNeeds Cleaning, Needs Further Evaluation
To view additional Lateral Sewer Line Photos, Click Here.
High Levels - Radon
High Levels - Radon

Radon Testing

Test Results

DEFICIENCY 14.1
High Levels - Radon

Average radon levels of 4.98pCi/L exceeded the 4 pCi/I EPA threshold. I recommend a longer test, up to 90 days, or installation of a mitigation system in the home.

Radon Testing Info

  • Test Results : Duration of Test95
  • Test Results : Average Radon Level4.98
  • Test Results : SummaryA full PDF breakdown of the radon test results is attached to this report. 
To view additional Radon Testing Photos, Click Here.